78
EVO-S, EVO-H MODULAR AIR HANDLING UNITS
OPERATION AND MAINTENANCE MANUAL
Table 13. Dimensions and quantities of metal and panel cassette lters
Size
EVO
W H Pcs. Size
EVO
W H Pcs.
[mm] [mm]
5100 605 350 1 5610 950 1150 2
3200 855 350 1 0020 1150 1150 2
5200 605 550 1 0120 850 1650 2
0300 855 450 1 5320 1150 1350 2
0400 1105 450 1 0720 950 1850 2
2500 1205 550 1 0230 898 1550 3
3500 855 800 1 0530 998 1550 3
0600 1205 650 1 0930 1150 2250 2
0700 700 650 2 0040 998 1850 3
5800 700 800 2 0050 1198 1850 3
8800 1105 1050 1 0060 1198 2250 3
0010 800 800 2 0070 1950 2350 2
5010 1205 1150 1 0090 1122 2650 4
5310 850 1050 2 0001 1197 2650 4
4410 700 1350 2 0021 1017 2950 5
4.2.3 Minipleat lters
M5 minipleat filters
M5 class minipleat filters are filters made of non-woven
fabric formed into filter packets in galvanized sheet cas-
ing; they are designed for preliminary air treatment.
M5 minipleat lters are 48mm deep. They are mounted in
straight SR type guides. Self-adhesive seals for sealing are
mounted on the walls of the air handling unit housing at
the point of lter adhesion and between cassettes, if there
are more lters.M5 minipleat lters are not to be regener-
ated and must be replaced with new ones. The dimensions
of the lters used are specied in the KT certicate.
Table 14. Dimensions and quantities of M5 minipleat lters
Size
EVO
In
practice
H
Amo-
unt
Size
EVO
In
practice
H
Amo-
unt
[mm] [mm]
5100 600 350 1 5610 473 1150 4
3200 424 350 2 0020 573 1150 4
5200 600 550 1 0120 565 1650 3
0300 424 450 2 5320 573 1350 4
0400 549 450 2 0720 473 1850 4
2500 599 550 2 0230 538 1550 5
3500 424 800 2 0530 598 1550 5
0600 599 650 2 0930 573 2250 4
0700 465 650 3 0040 598 1850 5
5800 465 800 3 0050 598 1850 6
8800 549 1050 2 0060 598 2250 6
0010 532 800 3 0070 555 2350 7
5010 599 1150 2 0090 560 2650 8
5310 565 1050 3 0001 597 2650 8
4410 465 1350 3 0021 564 2950 9
F7 and F9 minipleat filters
F7/F9 minipleat filters are filters made of non-woven fab-
ric formed into filter packets in galvanized sheet metal
casing; they are designed for secondary air treatment.
F7/F9 minipleat filters are 98mm deep. The frame for
mounting in a guide has a dimension of 25mm.
The filters are mounted in guides with seals and a slat
clamp that is locked on an eccentric connection mech-
anism (Fig. 42).
Separators from the metal section with seals are mounted
between the filters.
When replacing the filters, it is recommended to replace
the self-adhesive seal fixed inside the guide.
F7/F9 minipleat filters are not to be regenerated and must
be replaced with new ones.
The dimensions of the filters used are specified in the KT
certificate.
Table 15. Dimensions and quantities of F7/F9 minipleat lters
Size
EVO
W H Pcs.
Size
EVO
W H Pcs.
[mm] [mm]
5100 600 350 1 5610 473 1150 4
3200 424 350 2 0020 573 1150 4
5200 600 550 1 0120 565 821 6
0300 424 450 2 5320 573 1350 4
0400 549 450 2 0720 473 921 8
2500 599 550 2 0230 538 771 10
3500 424 800 2 0530 598 771 10
0600 599 650 2 0930 573 1121 8
0700 465 650 3 0040 598 921 10
5800 465 800 3 0050 598 921 12
8800 549 1050 2 0060 598 1121 12
0010 532 797 3 0070 555 1171 14
5010 599 1150 2 0090 560 1321 16
5310 565 1050 3 0001 598 1321 16
4410 465 1350 3 0021 564 1471 18
4.2.4 Bag lters
Bag filters are filters made of non-woven fabric formed
into pockets, which are fixed in a metal frame.
Bag filters are 300mm (G4 and M5) and 500mm (F7 and
F9) long. The frame is 25mm long. Depending on the
class, the bag filters have the appropriate number of bags.
G4 and M5 bag filters
The G4/M5 bag filters are designed for air pre-treatment.
They are mounted in straight SR type guides. Self-adhe-
sive seals for sealing are mounted on the walls of the air
handling unit housing at the point of filter adhesion and
between frames, if there are more filters.
G4/M5 bag filters are not to be regenerated and should
be replaced with new ones.
The dimensions of the filters used are specified in the KT
certificate.