From the measured differential pressure and the follo-
wing formula, the current air flow can be calculated (for
an air temperature of 20°C).
In case of multi-fan units, the stub is connected to one
of the fans.
Qv=n
w
k√(p
w
)
Qv - airflow rate [m3/h]
n
w
- number of fans in the set
k - characteristic coefficient for the fan
nozzle
p
w
- static pressure drop on the fan nozzle [Pa]
Fig. 72 Dierential pressure measurement scheme on the fan orice
Table 20 K-factors for ZIEHL-ABEGG and EBM-PAPST fan nozzles
Fan type K-factor Fan type K-factor
RH22C 47
R3G250RR01-H1 68
RH25C 60 R3G280-PR04-I1 77
RH28C 75 R3G310-AX54-21 116
RH31C 95 R3G355-AY43-21 148
RH35C 121 R3G400-PI92-01 188
RH40C 154 R3G450-PB24-01 240
RH45C 197 R3G500-PB33-01 281
RH50C 252 K3G630-PW04-01 438
RH56C 308 K3G710-PW06-01 545
RH63C 381 R3G250-PR17-I1 76
RH71C 490 R3G280-PS10-J1 77
R3G310-BB49-01 116
R3G355-PI93-01 148
R3G355-BC92-01 148
R3G400-AQ23-68 188
GR25C-6ID.BD.CR 60
GR31C-ZID.DC.CR 95
GR35C-ZID.DC.CR 121
4.10 UVC-S lamp
UVC-S lamps are designed to irradiation of the surfaces of
selected structural elements and devices installed inside
the unit
They are used in the cooling and ltration sections to irra-
diate:
• the surface of the lamellas of the coils from the air inlet side
and partly the condensate drip tray,
• lter inlet surface (dirty part).
Micro-suicidal protection is ensured by the use of high-per-
formance radiants producing in the light spectrum, a UVC
wavelength of approximately 254 nm. The radiant lumina-
ires are equipped with reector-directing reectors, which
increases their action. Lamp casing provide IP55 protection.
Most bacteria, mold and viruses are deactivated by long-
term UVC rays. The formation of biolm on their surfaces is
signicantly reduced, which shortens the chemical washing
process.
Inspection windows are additionally equipped with a lter
against the ingress of UVC light harmful to the eyes and
skin. Despite the lter used, however, it is not recommen-
ded to observe the space inside the UVC section for a long
time.
4.10.1 UVC-S lamp connection
UVC-S lamps must be electrically connected according to
the scheme. The lamps are powered by a single-phase vol-
tage of 230V / 50 Hz.
4.10.2 UVC-S lamp maintenance
Check the condition of the lamps periodically.
Maintaining cleanliness is important because its bacteri-
cidal eect may not be sucient to carry out disinfection.
If the UVC lamp uorescent lamp or the light reecting lamp
casing becomes dirty, clean it with a clean alcohol-stained
cloth, avoiding touching the glass parts with your hands.
The total operating time of UVC-S lamps is counted by the
automation system. After working the right number of ho-
urs, will appear the information about need to replace the
uorescent lamps and will display an alarm signal.
UVC light for sterilization is not visible to human vision, so
it is not possible to determine the correctness of its action
by observation.
It is recommended that the replacement of UVC-S uore-
scent lamps be carried out by an authorized KLIMOR service
center.
All components exposed to irradiation from
UVC lamps must be made of UVC-resistant
materials