Output Name Description Device type
AO6 COOLING_OUTPUT Analog Cooling Output 0-100% (0-10 V)
AO7 HEATING_OUTPUT Analog Heating Output 0-100% (0-10 V)
AO8 ECON_DAMPER Economizer Output 0-100% (0-10 V)
BO1 FAN Fan Start - Stop Unknown
BO2 COOL_STAGE_1 Cool Stage 1 Unknown
BO3 COOL_STAGE_2 Cool Stage 2 Unknown
BO4 HEAT_STAGE_1 Heat Stage 1 Unknown
BO5 HEAT_STAGE_2 Heat Stage 2 Unknown
Table 7–4 Roof top units
Output Name Description Device type
AO8 ECON_DAMPER Economizer Output 0-100% (0-10 V)
BO1 FAN Fan Start - Stop Unknown
BO2 COMPRESSOR_1 Stage 1 Compressor Unknown
BO3 COMPRESSOR_2 Stage 2 Compressor Unknown
BO4 REVERSING _VALVE Reversing Valve Unknown
BO5 AUXILIARY_HEAT Auxiliary Heat Unknown
Table 7–5 Heat pump units
Section 7: System integration KMC Controls, Inc.
116 Revision G