Setting the
commissioning
setpoints
The commissioning setpoints set the operational setpoints and limits for the
AppStat. The functions of the setpoints and how they are used are describe in
the topic Room temperature setpoints on page 66. Setting commissioning
setpoints requires entering Password2 which is described in the topic Enter
the commissioning mode on page 40.
Note: Not all setpoints in the following procedure are applicable to all models of
AppStat. Those setpoints are marked as (optional).
Procedure Steps Display
1 Starting display
1.
Start at the temperature display.
2.
Enter Password 2. The display changes to the
MAIN menu display.
F
°
70
AUTO AUTO
SECURITY
ADMIN LEVEL
0 0 0 0
2 Choose and set the
setpoints.
1.
From the MAIN menu , press either the or
button to select SETPOINTS.
2.
Press Enter. The SETPOINT menu opens
3.
Choose and set each of the following
setpoints.
Enter
Cncl
MAIN
SETPOINT
SCHEDULE
SYSTEM
COMM
ADVANCED
Procedure to set the commissioning setpoints
Installation, Operation, and Application Guide for AppStat Section 4: Commissioning functions
Revision G 41

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KMC Controls BAC-4000 series and is the answer not in the manual?

KMC Controls BAC-4000 series Specifications

General IconGeneral
BrandKMC Controls
ModelBAC-4000 series
CategoryController
LanguageEnglish

Related product manuals