Procedure Steps Display
10 Set the lockout
temperature for
auxiliary heat.
From the SYSTEM menu choose AUX HT
LOCKOUT to set the minimum outside air
temperature for auxiliary heat lockout. Auxiliary
heat will not operate above this temperature.
DelEnterCncl
AUX HT LOCKOUT:
60 °F
11 Set the compressor
low temperature
lockout.
From the SYSTEM menu choose COMP LOCK
TEMP to set the minimum outside air
temperature for compressor operation.
Compressors will not operate below this
temperature.
DelEnterCncl
COMP LOCK TEMP:
25 °F
12 Enable
dehumidification.
(Optional feature)
From the SYSTEM menu choose DEHUM
ENABLE to enable or disable dehumidification.
Dehumidification is only available on models
with a humidity sensor and auxiliary heat is
enabled.
BackEnterCncl
DEHUM ENABLE:
ENABLE
DISABLE
Set up heat pump unit system options (continued)
Installation, Operation, and Application Guide for AppStat Section 4: Commissioning functions
Revision G 59

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KMC Controls BAC-4000 series and is the answer not in the manual?

KMC Controls BAC-4000 series Specifications

General IconGeneral
BrandKMC Controls
ModelBAC-4000 series
CategoryController
LanguageEnglish

Related product manuals