2 TECHNICAL DATA
22
OPTISONIC 6300
www.krohne.com 09/2020 - 4006413102 - TD OPTISONIC 6300 V2 R02 en
PROFIBUS DP
PROFIBUS DPPROFIBUS DP
PROFIBUS DP
Description Galvanically isolated acc. to IEC 61158
Profile version: 3.02
Automatic data transmission rate recognition (max. 12 MBaud)
Bus address adjustable via local display at the measuring device
Function blocks 6 x analogue input block, 3 x totaliser function block, 1 x transducer
block, 1 x physical block
Output data Volume flow, mass flow, velocity of sound, flow speed, gain, SNR,
electronic temperature, power supply
Diagnostic data
(Further meas. values and diagnostic data is available via acyclic
access)
PROFIBUS PA
PROFIBUS PAPROFIBUS PA
PROFIBUS PA
Description Galvanically isolated acc. to IEC 61158
Profile version: 3.02
Current consumption: 10.5 mA
Permissible bus voltage: 9...32 V; in Ex application 9...24 V
Bus interface with integrated reverse polarity protection
Typical error current FDE (Fault Disconnection Electronic): 4.3 mA
Bus address adjustable via local display on the measuring device
Function blocks 6 x analogue input block, 3 x totaliser function block, 1 x transducer
block, 1 x physical block
Output data Volume flow, mass flow, velocity of sound, flow speed, gain, SNR,
electronic temperature, power supply
Diagnostic data
(Further meas. values and diagnostic data is available via acyclic
access)
FOUNDATION Fieldbus
FOUNDATION FieldbusFOUNDATION Fieldbus
FOUNDATION Fieldbus
Description Galvanically isolated acc. to IEC 61158
Current consumption: 10.5 mA
Permissible bus voltage: 9...32 V; in Ex application 9...24 V
Bus interface with integrated reverse polarity protection
Link Master function (LM) supported
Tested with Interoperable Test Kit (ITK) version 6.0
Function blocks 4 x analogue input, 2 x integrator, 1 x PID
Output data Volume flow, mass flow, flow speed, electronic temperature, velocity of
sound, gain, SNR
Diagnostic data

Other manuals for KROHNE OPTISONIC 6300