130
10 Appendix
10.18.2 Customer Interface
10.18.2.1Initial State
In the initial state (e.g. after power on) the display shows the condition of the ETAMATIC OEM
in the upper line (burner off, control operation, etc..) At the same time, queuing codes are cor-
rectly displayed ("Actuator runs")..
In the lower line of the display, it shows external and internal firing rate. If the parameter set-
tings of the burner firing rate controller is active, it shows setpoints and actual values of the
firing rate controller additionally.
In the initial state of the display (not on manual mode) while no fault of ETAMATIC OEM is
pending, the upper indicator line switches to:
call up flame intensity
press key F4 (M) twice
Without integral flame monitoring, the
display shows "---%"
mode switching O
2
-con-
trol ETAMATIC OEM
automatic
press key F4 (M) twice
O
2
fault reset status O
2
control Mode O
2
control, press key 11 (Enter),
recall fault history press key 7
call up text messages status O
2
control
press key 11 (Enter)
adjusting correction value firing-rate TK
O
2
control
press key 2 = excess air
press key 3 = air deficiency
changing O
2
setpoint
value
setpoint T
O
2
control
press key 7 = more O
2
press key 8 = less O
2
recall O
2
fault history status automatic press key 5 = browse fault history
press key 11 (Enter) = call text
changing firing-rate control-
ler setpoint
firing-rate operation
press keys 9 and 6 simultaneously,
when display is flashing, press keys 4
and 5 to adjust the setpoint, press key
11 (Enter) to store
Action Display
Mode Other
press the RESET key, to change the primary status.
Status display (operating mode) ETAMA-
TIC OEM
Fault history entry 1
...
...
...
Fault history entry 9
Fault history entry 10
•O
2
-Fault history entry 20
•O
2
-Fault history entry 19
...
...
...
•O
2
-Fault history entry 2
•O
2
-Fault history entry 1