6 Commissioning
6.1.16 Automatic Restart after Failure
Respect the directives for combustion plants, if you set this parameter.
Nr. FMS ETA
/FA1
Short Text Description Min Max Default
836 2 2 AutStart Automatic restart after fault 0 30 0
Automatic restart of the burner on fault condition. In the
case of a fault for which the standards permit an auto-
matic restart for FMS/ETAMATIC, this parameter initi-
ates the restart.
0 = no restart of the burner
1... = automatic restart of the burner for faults, which are
marked in the list of faults. (Delay in seconds)
Selection of the standard with P 425:
0 = TDR
1 = no restart of the burner
2 = EN676 (from 5.4/5f202)