6 Commissioning
6.5.1.4 Recalling Fault History
The ETAMATIC OEM stores the last 10 faults with the associated running time counter read-
ing.
Prerequisite: ETAMATIC OEM may not be in FAULT condition
With programming unit:
With customer interface:
NOTICE
If it is certain that the ETAMATIC OEM is fed with voltage at all the time since the last fault, it
is possible to determine at what time the fault occurred from the present running time counter
reading and the current clock time.
6.6 How to Change the Password
First enter the current password, see chapter 6.1.2 Password Entry
press key until the display shows STATUS
press key the display shows the latest error code
press ENTER key the display shows the associated plain text and running time
counter reading
press key again the display shows the second last error code
press key
press key the display shows the last error code
After 3 seconds, the display automatically shows a scrolling text with error code,
plain text and operating hours.
to terminate press key.
press key 3 and 2 to browse the fault history
press key "17" until the display shows "Status"
press keys 5, 7 and 9 simultaneously the display shows the entry field
for the new password
use keys 2 to 9, to set the new password
press key 16 until the display shows "digital inputs"
press Enter key