6 Commissioning
6 Commissioning
6.1 Before Commissioning
6.1.1 Basic Settings
First you must configure the device (ETAMATIC OEM) for the requirements of the system.
Therefore, you have to set the following parameters.
We recommend to use the LAMTEC PC software for Windows (available separately).
The factory standard settings are indicated by *.
For parameter settings, we recommend the usage of a seperately available PC software for
Windows.
6.1.2 Password Entry
By programming unit:
With the keys 9/8 the parameter content can be changed at 1.
With the keys 5/4 the parameter content can be changed at 100.
With the keys 3/2 the parameter content can be changed at 1000.
CAUTION!
A change does not need to be confirmed, it will be saved immediately.
Press key F3
Go to programming interface with keys 6 and 7
Confirm with key 11
Confirm warning with key F3
Press keys 5, 7 and 8 simultaneously
Enter password with keys 2....9 (0000 in delivery condition)
Press key 11 (Enter).
The display shows an arrow to the right and an arrow to the left above
the keys F2 and F3. This means the keys are in function.
Set "PARM" in the display with keys F2 and F3
Select the desired parameter with keys 6 or 7