Important codes for quick commissioning
8
Commissioning
8.6
L
8.6-5
EDS82EV903-1.0-11/2002
Code IMPORTANTPossible settings
No. SelectionLenzeName
C0034* Setpoint selection
range
Observe the switch position of the function
module!
^ 10.8-3
v
uSEr
Standard–I/O (X3/8)
35
0
0 Unipolar voltage 0 ... 5 V / 0 ... 10 V
Current 0 ... 20 mA
1 Current 4 ... 20 mA Changing the direction of rotation is only
possible with a digital signal.
2 Bipolar voltage -10 V ... +10 V • Minimum output fre quency (C0010) not
effective
• Individual adjustment of offset and gain
3 Current 4 ... 20 mA open-circuit monitored TRIP S d5, if I < 4 mA
Changing the direction of rotation is only
possible with a digital signal.
C0034*
v
(A)
uSEr
Setpoint selection
range
Applicat ion I/O
Observe the jumper setting of the function
module!
^ 10.8-3
1 X3/1U, X3/1I
0
0 Unipolar voltage 0 ... 5 V / 0 ... 10 V
2 X3/2U, X3/2I 1 Bipolar voltage -10 V ... +10 V Minimum output f re quency (C0010) not
effective
2 Current 0 ... 20 mA
3 Current 4 ... 20 mA Changing the direction of rotation is only
possible with a digital signal.
4 Current 4 ... 20 mA open-circuit monitored Changing the direction of rotation is only
possible with a digital signal.
TRIP Sd5 if I < 4 mA
C0037 JOG1 20.00 -650.00 {0.02 Hz} 650.00
JOG = Setpoint ^ 10.8-13
C0038 JOG2 30.00 -650.00 {0.02 Hz} 650.00
Additional JOG frequencies ð C0440
C0039 JOG3 40.00 -650.00 {0.02 Hz} 650.00
C0050*
uSEr
Output frequency
(MCTRL1-NOUT)
-650.00 {Hz} 650.00 Only display: Output frequency without slip
compensation
C0087 Rated motor speed à 300 {1 rpm} 16000 à Depending on the controller ^ 10.9-1
C0088 Rated motor
current
à 0.0 {0.1 A} 650.0 à Depending on the controller
0.0 ... 2.0 x rated output current of the
controller
^ 10.9-1
C0089 Rated motor
frequency
50 10 {1 Hz} 960 ^ 10.9-1
C0090 Rated motor
voltage
à 50 {1 V} 500 à 230 V with 230 V controllers,
400 V with 400 V controllers
^ 10.9-1
C0091 Motor cos j à 0.40 {0.1} 1.0 à Depending on the controller ^ 10.9-1
C0119 Configuration of 0
0 PTC input not active
Earth fault detection • Signal output configuration under C0415 ^ 10.14-3
v
36
motor temperature
monitoring (PTC
1 PTC input active,
TRIP set
active
• If several parameter sets are used, the
monitoring must be separately adjusted
nput
eart
au
t
detection
2 PTC input active,
Warning set
for each parameter set.
• Deactivate the earth fault detection, if it
3 PTC input not active
Earth fault detection
.
• If the earth fault detection is active, the
4 PTC input active,
TRIP set
,
motor starts after controller enable with
a delay of approx.40 ms.
5 PTC input active,
Warning set
C0140* Additive frequency
setpoint
(NSET1-NADD)
0.00 -650.00 {0.02 Hz} 650.00 • Selection via function j of the
keypad or the parameter channel
• Is added to main setpoint
• Value is stored when switching the
mains or removing the keypad
^ 10.8-15