Operation with increased rated power
Rated data for mains voltage 230 V
4
Technical data
4.4
4.4.1
L
4.4-3
EDS82EV903-1.0-11/2002
Operation without mains choke
Installatio n t o EN 60204-1 Installation to UL
1)
8200 vector Mains L1, L2, L3,
PE
L1, L2, L3,
PE
FI
Type [kW] [mm
2
] [AWG]
E82EV251K2C 0.25
M10 A C10 A 1.5 10 A 16
E82EV551K2C 0.55
1/N/PE AC
Operation only with mains choke
E82EV751K2C 0.75
180 ... 264
;
Operation only with mains choke
≥ 30 m
E82EV152K2C 1.5
45 ... 65 Hz
M20 A B20 A 2x1.5 20 A 2x16
E82EV551K2C 0.55 Operation only with mains choke
E82EV751K2C 0.75
3
PE
C
Operation only with mains choke ≥ 30 mA
3)
E82EV152K2C 1.5
100 ... 264 V; M16 A B16 A 2.5 15 A 14
E82EV302K2C 3.0
45 ... 65 Hz
M25 A B25 A 4 25 A 10
≥ 300 m
4)
E82EV552K2C 5.5
Operation only with mains choke
≥ 30 mA
5)
Operation with mains choke
Installatio n t o EN 60204-1 Installation to UL
1)
8200 vector Mains L1, L2, L3,
PE
L1, L2, L3,
PE
FI
Type [kW] [mm
2
] [AWG]
E82EV251K2C 0.25
M10 A C10 A 1.5 10 A 16
E82EV551K2C 0.55
1/N/PE AC
M10 A B10 A 1.5 10 A 16
E82EV751K2C 0.75
180 ... 264
;
M10 A B10 A 1.5 10 A 16
≥ 30 m
E82EV152K2C 1.5
45 ... 65 Hz
M16 A B16 A 2x1.5 15 A 2x16
E82EV551K2C 0.55 M6 A B6 A 1 5A 18
E82EV751K2C 0.75
3
PE
C
M10 A B10 A 1.5 10 A 16 ≥ 30 mA
3)
E82EV152K2C 1.5
100 ... 264 V; M10 A B10 A 1.5 10 A 16
E82EV302K2C 3.0
45 ... 65 Hz
M20 A B20 A 4 20 A 12
≥ 300 m
4)
E82EV552K2C 5.5
M32 A B32 A 6
6)
35 A 8
≥ 30 mA
5)
Fuse
E.l.c.b.
1)
Use UL-approved cables, fuses and fuse holders only.
UL fuse: voltage 240 V, tripping characteristic ”H” or ”K5”
2)
Pulse-current or universal-current sensitive earth leakage circuit breaker
3)
All-current sensitive e.l.c.b.
4)
All-current sensitive e.l.c.b. for use with E82EVxxxK2C0xx
5)
All-current sensitive e.l.c.b. for use with E82EVxxxK2C2xx
6)
Flexible cable can only be connected using pin end connectors.
Observe national and re gional regulations (e. g. VDE 0113, EN 60204)
Fuses and cable cross-sections
(operation with increases rated
power, mains voltage 230 V)