Parameter data transfer
Writing parameters to the inverter
64
Lenze · E84AYCER communication module (PROFINET) · EDS84AYCER EN 3.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.1 Response to a correctly executed write request
Response header
9.3.2 Response to a write error
Byte 1 Byte 2 Byte 3 Byte 4
Request reference
(mirrored)
Response identification Axis
(mirrored)
Number of indices
Field Data type Values
Request reference U8 Mirrored value of the parameter request
Response identification U8 0x01: Parameter written
Axis U8 0x00 or 0x01
Number of indices U8 0x"n" (n = number of parameters requested)
Note!
In the case of a multi-parameter request, correct and possible faulty messages are sum-
marised in one frame. They have the following data contents:
Correct message
Format: 0x40
Number of values: 0x00
Faulty message
Format: 0x44
Number of values: 0x01 or 0x02
Error code without additional information (number of values = 0x01) or
Error code with additional information (number of values = 0x02)
A faulty access to a parameter "n" is indicated at the nth position in the response frame
of a multi-parameter request.