EasyManua.ls Logo

Lenze E84AYCER - Diagnostic Data Structure

Lenze E84AYCER
101 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Lenze · E84AYCER communication module (PROFINET) · EDS84AYCER EN 3.0 - 02/2019 78
Diagnostics
Diagnostic data
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.3 Diagnostic data
The I/O device sends an alarm message to the I/O controller to signalise the diagnostic data be-
low.
Errors and warnings of the Inverter Drive 8400 and the module connected to it are sent to the
IO controller as extended diagnostic messages.
With code C13887
, the transmission of an alarm message can be suppressed for specific error
messages.
The diagnostic data can be displayed using the hexadecimal representation of the Siemens S7
engineering tool.
Bytes Meaning Value [hex]
1 ... 6 Diag. block header 0x0010 001C 0100
7 ... 8 Alarm type 0x0001 (diagnosis)
9 ... 12 API 0x0000 0000
13, 14 Slot number 0x0001 / 0x0002
15, 16 Subslot number 0x0001
17 ... 20 Module ID ID according to module
21 ... 24 Submodule ID ID according to module
25, 26 Alarm specifier 0xB000
27, 28 User structure identifier 0x0001
29 ... 32 Error code of the Inverter Drive 8400 / E84AYCER