Parameter reference
Parameters of the communication module
93
Lenze · E84AYCER communication module (PROFINET) · EDS84AYCER EN 3.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13885
C13887
C13899
Parameter | Name:
C13885 | Clear process data
Data type: UNSIGNED_8
Index: 10690
d
= 29C2
h
This code is used to set the process data that are to be processed by the I/O device in order to maintain the internal
communication when the PROFINET has left the DATA_EXCHANGE status.
Selection list (Lenze setting printed in bold) Info
0 Use of most recent master PDOs The last data sent by the I/O controller are used.
1 PDOs are set to the value 0' The contents of the process data are set to the value "0".
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13887 | Suppress signalling diag. mess. upon
Data type: BITFIELD_8
Index: 10688
d
= 29C0
h
This code serves to inhibit the transmission of alarm messages to the IO controller. By this, errors of a specific type
can be systematically suppressed. All errors are furthermore entered in the logbook.
• A change will only be effective immediately if no error number with the error type selected here is active in stan-
dard device code C00165.
Value is bit-coded: Info
Bit 0 Error
Bit 1 Fault
Bit 2 Quick stop by trouble
Bit 3 Warning Locked
Bit 4 Warning
Bit 5 Information
Bit 6 Reserved
Bit 7 Connection to 8400 lost
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13899 | Station name
Data type: VISIBLE_STRING
Index: 10676
d
= 29B4
h
The name with a max. length of 240 characters is distributed to the subindices. The name can be entered starting
with subindex 1. The following unused subindices are not relevant.
• The station name must be assigned in accordance with the PROFINET specification. In the standard setting a de-
leted name is displayed. The name is also deleted if the "Reset to factory defaults" command is executed by an
IO supervisor or an I/O controller.
• A change of the station name will only become effective by switching the mains of the inverter.
Setting the station name
( 36)
Subcodes Lenze setting Info
C13899/1 1st ... 30th character
C13899/2 31th ... 60th character
C13899/3 61th ... 90th character
C13899/4 91th ... 120th character
C13899/5 121th ... 150th character
C13899/6 151th ... 180th character
C13899/7 181th ... 210th character
C13899/8 211th ... 240th character
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT