Parameter reference
Parameters of the communication module
93
Lenze · E84AYCER communication module (PROFINET) · EDS84AYCER EN 3.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13885
C13887
C13899
Parameter | Name:
C13885 | Clear process data
Data type: UNSIGNED_8
Index: 10690
d
= 29C2
h
This code is used to set the process data that are to be processed by the I/O device in order to maintain the internal
communication when the PROFINET has left the DATA_EXCHANGE status.
Selection list (Lenze setting printed in bold) Info
0 Use of most recent master PDOs The last data sent by the I/O controller are used.
1 PDOs are set to the value 0' The contents of the process data are set to the value "0".
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13887 | Suppress signalling diag. mess. upon
Data type: BITFIELD_8
Index: 10688
d
= 29C0
h
This code serves to inhibit the transmission of alarm messages to the IO controller. By this, errors of a specific type
can be systematically suppressed. All errors are furthermore entered in the logbook.
A change will only be effective immediately if no error number with the error type selected here is active in stan-
dard device code C00165.
Value is bit-coded: Info
Bit 0 Error
Bit 1 Fault
Bit 2 Quick stop by trouble
Bit 3 Warning Locked
Bit 4 Warning
Bit 5 Information
Bit 6 Reserved
Bit 7 Connection to 8400 lost
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13899 | Station name
Data type: VISIBLE_STRING
Index: 10676
d
= 29B4
h
The name with a max. length of 240 characters is distributed to the subindices. The name can be entered starting
with subindex 1. The following unused subindices are not relevant.
The station name must be assigned in accordance with the PROFINET specification. In the standard setting a de-
leted name is displayed. The name is also deleted if the "Reset to factory defaults" command is executed by an
IO supervisor or an I/O controller.
A change of the station name will only become effective by switching the mains of the inverter.
Setting the station name
( 36)
Subcodes Lenze setting Info
C13899/1 1st ... 30th character
C13899/2 31th ... 60th character
C13899/3 61th ... 90th character
C13899/4 91th ... 120th character
C13899/5 121th ... 150th character
C13899/6 151th ... 180th character
C13899/7 181th ... 210th character
C13899/8 211th ... 240th character
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT