Lenze · E84AYCER communication module (PROFINET) · EDS84AYCER EN 3.0 - 02/2019 92
Parameter reference
Parameters of the communication module
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13878
C13880
C13881
Parameter | Name:
C13878 | Bus error(2)
Data type: BITFIELD_16
Index: 10697
d
= 29C9
h
The code contains the error currently detected on the fieldbus.
The error values can occur in combination with the error values from code C13877
.
Value is bit-coded: Info
Bit 0 Reserved
... ...
Bit 6 Reserved
Bit 7 IP address error
Bit 8 Station name error
Bit 9 DataExch left
Bit 10 Stack boot error
Bit 11 Stack online error
Bit 12 Stack state error
Bit 13 Stack revision error
Bit 14 Stack init error
Bit 15 Stack CPU boot error
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13880 | Monitoring Reaction
Data type: UNSIGNED_8
Index: 10695
d
= 29C7
h
The action set in subcode 1 of the code is carried out when the node recognises that it is no longer in the
DATA_EXCHANGE status.
Please also observe the notes provided in code C13881
.
A change in the monitoring response becomes immediately effective.
Selection list
0 No response
1 Error
3 Quick stop by trouble
4 Warning Locked
6 Information
Subcodes Lenze setting Info
C13880/1 0: No Response "Watchdog/Data Exchange" monitoring
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13881 | Reaction time delay
Data type: UNSIGNED_16
Index: 10694
d
= 29C6
h
If the DATA_EXCHANGE status is exited, the response parameterised in C13880 is activated after the time set here
has elapsed.
A value of "65535" in this code deactivates the monitoring function.
A change of monitoring will be effective immediately.
Setting range (min. value | unit | max. value) Lenze setting
0 ms 65535 0ms
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT