Parameter reference
Parameters of the communication module
91
Lenze · E84AYCER communication module (PROFINET) · EDS84AYCER EN 3.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13867
C13877
Parameter | Name:
C13867 | Display: Most recent diagnostic data
Data type: OCTET_STRING
Index: 10708
d
= 29D4
h
Display of the diagnostic data sent by the inverter most recently.
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Bytes Information
0Slot
1
2Subslot
3
4 Error code
...
7
8Slot
9
10 Subslot
11
12 Error code
...
15
Parameter | Name:
C13877 | Bus error(1)
Data type: UNSIGNED_16
Index: 10698
d
= 29CA
h
The code contains the error currently detected on the fieldbus.
The error values can occur in combination with the error values from code C13878
.
Selection list (read only) Info
0 No error
1 Internal error
2 Unit ID unknown
3 Max. units exceeded
4 Invalid size
5 Unit type unknown
6 Runtime plug
7 Invalid argument
8 Service pending
9 Stack not ready
10 Command unknown
11 Invalid address descriptor
12 Watchdog expired
13 Protocol not supported
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT