8400 BaseLine D | Software Manual
Parameter reference
Parameter list | C00024 |
180 L Firmware 03.00 - DMS EN 5.0 - 07/2009
C00024 |
C00026
C00027
C00028 |
Parameter | Name:
C00024 | Comparison value N_Act
Data type: INTEGER_16
Index: 24551
d
= 5FE7
h
Threshold for the actual speed comparison
This parameter serves to set a threshold that is compared with the actual speed value.
When the value falls below this threshold, the bNactCompare output of the SB LS_DriveInterface
switches to
TRUE.
Switching hysteresis = +1 %
Setting range (min. value | unit | max. value) Lenze setting
0.0 % 199.9 0.0 %
; Read access ; Write access CINH PLC STOP No Transfer COM MOT Scaling factor: 100
Parameter | Name:
C00026 | AINx: Offset
Data type: INTEGER_16
Index: 24549
d
= 5FE5
h
Offset for analog input
I/O terminals
Setting range (min. value | unit | max. value)
-199.9 % 199.9
Subcodes Lenze setting Info
C00026/1 0.0 % AIN1: Offset
; Read access ; Write access CINH PLC STOP No Transfer COM MOT Scaling factor: 100
Parameter | Name:
C00027 | AINx: Gain
Data type: INTEGER_32
Index: 24548
d
= 5FE4
h
Gain for analog input
I/O terminals
Setting range (min. value | unit | max. value)
-199.9 % 199.9
Subcodes Lenze setting Info
C00027/1 100.0 % AIN1: Gain
; Read access ; Write access CINH PLC STOP No Transfer COM MOT Scaling factor: 100
Parameter | Name:
C00028 | AINx: Input voltage
Data type: INTEGER_16
Index: 24547
d
= 5FE3
h
Display of the input voltage at the analog input
I/O terminals
Display range (min. value | unit | max. value)
-10.0 V 10.0
Subcodes Info
C00028/1 AIN1: Input voltage
; Read access Write access CINH PLC STOP ; No Transfer COM MOT Scaling factor: 100