EasyManua.ls Logo

Lenze L-force 8400 BaseLine D - Page 179

Lenze L-force 8400 BaseLine D
228 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Firmware 03.00 - DMS EN 5.0 - 07/2009 L 179
8400 BaseLine D | Software Manual
Parameter reference
Parameter list | C00018 |
C00018 |
C00019
C00021
C00022 |
C00023
Parameter | Name:
C00018 | Switching frequency
Data type: UNSIGNED_8
Index: 24557
d
= 5FED
h
Selection of the pulse width modulated switching frequency transferred from the inverter to the motor
When a variable switching frequency is selected, the switching frequency may change as a function of the load
and rotational frequency.
Selection list (Lenze setting printed in bold)
1 4 kHz var./drive-optimised
28 kHz var./drive-optimised
3 16 kHz var./drive-optimised
5 2 kHz constant/drive-optimised
6 4 kHz constant/drive-optimised
7 8 kHz constant/drive-optimised
8 16 kHz constant/drive-optimised
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00019 | Auto-DCB: Threshold
Data type: UNSIGNED_16
Index: 24556
d
= 5FEC
h
Setpoint speed threshold for the automatic DC injection brake
For speed setpoints with values below the thresholds a DC current is injected or the motor is not supplied with
current, depending on the setting.
Setting range (min. value | unit | max. value) Lenze setting
0 rpm 9999 3rpm
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00021 | Slip comp.
Data type: INTEGER_16
Index: 24554
d
= 5FEA
h
Slip compensation for VFCplus and SLVC operating modes
An increase of the slip compensation causes a greater frequency and voltage increase when the machine is load-
ed.
After the motor to be used has been selected from the motor catalogue, the suitable value can be entered auto-
matically. An automatic detection via the motor parameter identification is possible as well.
Motor control (MCTRL)
: Optimising the operational performance by slip compensation
Setting range (min. value | unit | max. value) Lenze setting
-50.00 % 50.00 0.00 %
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00022 | Imax in motor mode
Data type: UNSIGNED_16
Index: 24553
d
= 5FE9
h
Maximum current in motor mode for all operating modes
Setting range (min. value | unit | max. value) Lenze setting
0.00 A 99.99 47.00 A
; Read access ; Write access CINH PLC STOP No Transfer COM MOT Scaling factor: 100
Parameter | Name:
C00023 | Imax in generator mode
Data type: INTEGER_16
Index: 24552
d
= 5FE8
h
Maximum current in generator mode for all operating modes
•100% Imax in motor mode (C00022
)
Setting range (min. value | unit | max. value) Lenze setting
0.0 % 100.0 100.0 %
; Read access ; Write access CINH PLC STOP No Transfer COM MOT Scaling factor: 100

Table of Contents

Related product manuals