8400 BaseLine D | Software Manual
Parameter reference
Parameter list | C00039 |
182 L Firmware 03.00 - DMS EN 5.0 - 07/2009
C00039 |
C00050 |
C00051 |
C00052 |
C00053 |
Parameter | Name:
C00039 | Fixed setpoint x (L_NSet_1 n-Fix)
Data type: INTEGER_16
Index: 24536
d
= 5FD8
h
FB L_NSet_1: Fixed speed setpoints (Jog values) for the setpoint generator
Setting range (min. value | unit | max. value)
-199.9 % 199.9
Subcodes Lenze setting Info
C00039/1 40.0 % Fixed setpoint 1
C00039/2 60.0 % Fixed setpoint 2
C00039/3 80.0 % Fixed setpoint 3
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00050 | MCTRL: Speed setpoint
Data type: INTEGER_32
Index: 24525
d
= 5FCD
h
Display of the speed setpoint at the speed setpoint input of the motor control.
Display range (min. value | unit | max. value)
-9999 rpm 9999
; Read access Write access CINH PLC STOP ; No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00051 | MCTRL: Actual speed value
Data type: INTEGER_32
Index: 24524
d
= 5FCC
h
Display of the actual speed value of the motor shaft
Note:
The displayed value only corresponds to the real actual speed value of the motor shaft if an encoder is connected to
the motor and the evaluation of the feedback signal has been set correctly ("Closed loop" operation).
In case of operation without feedback, the signal is calculated from the motor control and thus may not correspond
to the real actual speed.
Display range (min. value | unit | max. value)
-9999 rpm 9999
; Read access Write access CINH PLC STOP ; No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00052 | Motor voltage
Data type: UNSIGNED_16
Index: 24523
d
= 5FCB
h
Display of the current motor voltage/output voltage of the inverter
Display range (min. value | unit | max. value)
0 V 1000
; Read access Write access CINH PLC STOP ; No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00053 | DC-bus voltage
Data type: UNSIGNED_16
Index: 24522
d
= 5FCA
h
Display of the current DC-bus voltage
Display range (min. value | unit | max. value)
0 V 1000
; Read access Write access CINH PLC STOP ; No transfer COM MOT Scaling factor: 1