8400 BaseLine D | Software Manual
Parameter reference
Parameter list | C00910
218 L Firmware 03.00 - DMS EN 5.0 - 07/2009
C00910
C00990
C00991
C00992
C00994
Parameter | Name:
C00910 | Frequency limitation
Data type: UNSIGNED_16
Index: 23665
d
= 5C71
h
Maximum positive/negative output frequency for all operating modes
Setting range (min. value | unit | max. value)
0 Hz 300
Subcodes Lenze setting Info
C00910/1 300 Hz Max. pos. output frequency
C00910/2 300 Hz Max. neg. output frequency
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00990 | Flying restart fct.: Activation
Data type: UNSIGNED_8
Index: 23585
d
= 5C21
h
Switch on/activate flying restart circuit for non-feedback drive systems
Selection list (Lenze setting printed in bold)
0Off
1On
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00991 | Flying restart fct.: Process
Data type: UNSIGNED_16
Index: 23584
d
= 5C20
h
Selection of the starting value and the speed search range for the flying restart function
Selection list (Lenze setting printed in bold)
5 -n...+n | Last output frequency
6 -n...+n | Actual setpoint frequency
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00992 | Flying restart: start frequency
Data type: INTEGER_16
Index: 23583
d
= 5C1F
h
Selection of the starting value for the flying restart function
Setting range (min. value | unit | max. value) Lenze setting
-200 Hz 200 10 Hz
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00994 | Flying restart fct.: Current
Data type: INTEGER_16
Index: 23581
d
= 5C1D
h
Current to be injected during the flying restart process
•100% rated motor current (C00081
).
The flying restart current is to amount to 10 ... 25 % of the rated motor current.
Setting range (min. value | unit | max. value) Lenze setting
0.0 % 100.0 25.0 %
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100