Parameter list | C00064
184 L Firmware 03.00 - DMS EN 5.0 - 07/2009
C00064
C00066
C00073
C00074
C00081
Parameter | Name:
C00064 | Device utilisation (Ixt)
Data type: INTEGER_16
Index: 24511
d
= 5FBF
h
Display of the device utilisation Ixt in different time resolutions
• If the value displayed here exceeds the threshold set in C00123
, the fault message "OC5: Device overload (Ixt)"
is output and the fault response set in C00604
is executed (default setting: "Warning").
Display range (min. value | unit | max. value)
0 % 250
Subcodes Info
C00064/1 Device utilisation (Ixt)
• Maximum value of the pulse utilisation (C00064/2)
and permanent utilisation (C00064/3).
C00064/2 Device utilisation (Ixt) 15s
• Pulse utilisation via the last 15 seconds (only for loads
>160 %).
C00064/3 Device utilisation (Ixt) 3min
• Permanent utilisation via the last 3 minutes.
; Read access Write access CINH PLC STOP ; No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00066 | Thermal motor load (I²xt)
Data type: INTEGER_16
Index: 24509
d
= 5FBD
h
Display of the thermal motor load being detected sensorless via a motor model
• If the value displayed here exceeds the threshold set in C00120
, the fault message "OC6: Device overload (Ixt)"
is output and the fault response set in C00606
is executed (default setting: "Warning").
Display range (min. value | unit | max. value)
0 % 200
; Read access Write access CINH PLC STOP ; No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00073 | Vp Imax controller
Data type: UNSIGNED_16
Index: 24502
d
= 5FB6
h
Gain factor Vp for Imax controller
Setting range (min. value | unit | max. value) Lenze setting
0.00 16.00 0.25
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT Scaling factor: 100
Parameter | Name:
C00074 | Ti Imax controller
Data type: UNSIGNED_16
Index: 24501
d
= 5FB5
h
Reset time Ti for Imax controller
Setting range (min. value | unit | max. value) Lenze setting
12 ms 9990 65 ms
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT Scaling factor: 1
Parameter | Name:
C00081 | Rated motor power
Data type: UNSIGNED_16
Index: 24494
d
= 5FAE
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Note:
It is mandatory to give the rated motor power for the field-oriented operating mode (SLVC).
Setting range (min. value | unit | max. value) Lenze setting
0.00 kW 99.00 11.00 kW
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT Scaling factor: 100