Firmware 03.00 - DMS EN 5.0 - 07/2009 L 185
8400 BaseLine D | Software Manual
Parameter reference
Parameter list | C00084
C00084
C00085
C00087
C00088
C00089
Parameter | Name:
C00084 | Motor stator resistance
Data type: UNSIGNED_32
Index: 24491
d
= 5FAB
h
After the motor to be used has been selected from the motor catalogue, the suitable value can be entered automat-
ically. An automatic detection via the motor parameter identification is possible as well.
Setting range (min. value | unit | max. value) Lenze setting
0 mOhm 200000 330 mOhm
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT Scaling factor: 1
Parameter | Name:
C00085 | Motor stator leakage inductance
Data type: UNSIGNED_16
Index: 24490
d
= 5FAA
h
After the motor to be used has been selected from the motor catalogue, the suitable value can be entered automat-
ically. An automatic detection via the motor parameter identification is possible as well.
Setting range (min. value | unit | max. value) Lenze setting
0.00 mH 650.00 0.00 mH
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT Scaling factor: 100
Parameter | Name:
C00087 | Rated motor speed
Data type: UNSIGNED_16
Index: 24488
d
= 5FA8
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Note:
It is mandatory to give the rated motor speed for the field-oriented operating mode (SLVC).
Setting range (min. value | unit | max. value) Lenze setting
50 rpm 9999 1460 rpm
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT Scaling factor: 1
Parameter | Name:
C00088 | Rated motor current
Data type: UNSIGNED_16
Index: 24487
d
= 5FA7
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Setting range (min. value | unit | max. value) Lenze setting
0.00 A 99.00 21.00 A
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT Scaling factor: 100
Parameter | Name:
C00089 | Rated motor frequency
Data type: UNSIGNED_16
Index: 24486
d
= 5FA6
h
This value can be obtained from the motor nameplate. After the motor to be used has been selected from the motor
catalogue, the suitable value can be entered automatically.
Note:
It is mandatory to give the rated motor frequency for the field-oriented operating mode (SLVC).
Setting range (min. value | unit | max. value) Lenze setting
10 Hz 1000 50 Hz
; Read access ; Write access CINH PLC STOP No transfer COM ; MOT Scaling factor: 1