Controller commands
Certain commands can only be executed if the controller is inhibited, e.g.
• Load Lenze setting C002/1
• Load parameter set 1, C002/7
• Identify motor parameters C002/23
If these commands are executed without the controller being inhibited, the returned
information is:
"6": No access controller inhibit
Note!
C003 always displays the last error occurred in the form of an error number, if
e.g. a command should fail.
Status display for device command
( 57)