Firmware 03.00 - DMS EN 5.0 - 07/2009 L 77
8400 BaseLine D | Software Manual
Motor control (MCTRL)
Selection of the operating mode
Setting the V/f base frequency
The V/f base frequency determines the slope of the V/f characteristic and has considerable
influence on the current, torque, and power performance of the motor.
The setting in code C015
applies to all permissible mains voltages.
Mains fluctuations or fluctuations of the DC-bus voltage (operation in generator
mode) do not need to be considered when the code is set. They are automatically
compensated by the internal mains voltage compensation of the device.
Depending on the setting of C015
it may be necessary to adapt the reference speed
C011
to be able to run through the whole motor speed range.
The V/f base frequency is automatically calculated from the data stored in the motor
nameplate by the motor parameter identification:
Typical values for the V/f base frequency C015
:
•V
frequency inverter
:
Frequency inverter 400 V
Frequency inverter 230 V
•V
ratedmot
: Rated motor voltage depending on the
connection method
•f
rated
: Rated motor frequency
Frequency inverter 400 V Frequency inverter 230 V
Motor
voltage [V]
Motor
frequency
[Hz]
Motor
connection
C015 Motor
voltage [V]
Motor
frequency
[Hz]
Motor
connection
C015
230 / 400 50 50 Hz 230 50 50 Hz
220 / 380 50 52.6 Hz 220 / 380 50 52.3 Hz
280 / 480 60 50 Hz
400 / 690
400
50
50
50 Hz
230 / 400
280 / 480
400
50
60
87
87 Hz
220 / 380 50 90.9 Hz
Note!
4-pole asynchronous motors, which are designed for a rated frequency of f = 50
Hz in star connection, can be operated in delta connection when being
constantly excited up to f = 87 Hz.
Advantages:
Higher speed-setting range
73% higher power output in case of standard motors
Motor current and motor power increase by the factor .
The field weakening range starts above 87 Hz.
Generally, this process can also be used with motors which have different
numbers of pole pairs. In case of 2-pole asynchronous motors, the mechanical
limit speed must be maintained.
C00015 Hz[]
U
freq inv,
V[]
U
ratedmot
V[]
---------------------------------- -
f
rated
Hz[]=
3