Error No. Description Details Causes
09 Indoor unit EEPROM error.
• Serial number on
EEPROM of indoor
unit is 0 or FFFFFF.
• Communication error
between MICOM and
EEPROM.
• Indoor unit PCB EE-
PROM is in error or
data is not available.
1. Error developed in transmission between the microproces-
sor and the EEPROM on the indoor unit PCB.
2. EEPROM is damaged.
Replace the indoor unit PCB, perform the Auto Addressing procedure, and input the central control address.