199
Error Codes
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Please refer to the Safety Precautions on pages 4-7 for more detail to prevent injury or death regarding the operation and service
troubleshooting of the Multi V product.
WARNING
ERROR CODES
Error No. Description Details Causes
194
Master: 1941
Slave 1: 1942
Slave 2: 1943
Outdoor unit fan
heatsink tempera-
ture sensor error.
Disconnection or short circuit of outdoor unit
fan heatsink temperature sensor.
1. Check sensor connection.
2. Sensor is shorted or open.
3. Defective outdoor unit PCB.
Are the temperature sensor
connections correct?
Check and fix connections.
No
Yes
Is the temperature sensor
resistance value normal?
No
Replace outdoor unit PCB.
Replace sensor.
Yes
,IWKHYDOXHLV!NȍRSHQRUȍVKRUWWKHUHLVDQHUURU
Sensor resistance value will vary with the temperature. See below for the resistance values according to temperature (±5% tolerance).
$LUWHPSHUDWXUHVHQVRU) Nȍ) Nȍ) Nȍ
3LSHWHPSHUDWXUHVHQVRU) Nȍ) Nȍ) Nȍ
Error No. 194