Operator Control and Display Panel
90 Liebert
®
NX
10.11 UPS Status Messages
The Liebert NX displays status changes as they occur in the current status window of the LCD,
then stores that data in the history log, as shown in Figure 61.
Current Status Window: The status messages are displayed chronologically and include the
date and time of the events. Three status messages are visible in the window at a time. To see
other messages, use the navigation keys to scroll up or down the list. A status message remains in
the current status area of the LCD until the status changes, when it is moved to the history log.
History Log: When a record moves to the history log, the time the status changed is recorded.
The history log can hold up to 512 records. History log records may be viewed by accessing the
Records menu.
Figure 61 Current status and history log records
See Appendix A for a complete list of status messages, along with a description and any
recommended actions.
?
Language
Battery
History
Inverter in setting
2003-01-21 12 :21 :12
2003-01-21 12 :21 :12
UPS shutdown
2003 -01 -21 12 :21 :12
2003 -01 -22 12 :30 :16
Bypass abnormal
2003 -01 -21 12 :21 :12
2003 -01 -21 12 :30 :16
F2 F4 HELPF1 F3
Liebert NX
2007-01-12 12:30:36
80KVA-3X3
Single Normal
Input disconnect closed 01-12 12:30
Output disconnect closed 01-12 12:30
Bypass disconnect open 01-12 12:30
History Log
(records
menu)
Current
Status
Messages

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Liebert NX and is the answer not in the manual?

Liebert NX Specifications

General IconGeneral
Frequency50/60 Hz
TopologyDouble Conversion/Online
Input Voltage208, 220, 240 VAC
Output Voltage208, 220, 240 VAC
Battery TypeVRLA
Operating Temperature0 to 40°C (32 to 104°F)
Humidity Range0 to 95% (non-condensing)