9.0 OPERATION
9.1 General Description
Liebert’s NX provides continuous, high-quality AC power to your business-critical equipment, such as
telecommunications and data processing equipment. The Liebert NX UPS supplies power that is free
of the disturbances and variations in voltage and frequency common to utility power, which is subject
to brownouts, blackouts, surges and sags.
The Liebert NX utilizes the latest in high-frequency, double-conversion pulse width modulation
technology and fully digital controls to enhance its reliability and increase the ease of use.
Specifically, the Liebert NX 480V utilizes soft-switching technology to greatly enhance efficiency.
As shown in Figure 51, the AC utility source is input at CB1 and the rectifier converts the AC utility
into DC power. The inverter converts that DC power from the utility—or DC power from the
batteries—into AC power for the load. The batteries power the load through the inverter in the event
of a power failure. The utility source can also power the load through the static bypass.
If maintenance or repair of the UPS is necessary, the load can be switched without interruption in
service to the maintenance bypass.
Figure 51 Single module block diagram (dual input configuration)
3-Phase
3W + Gnd
3-Phase
3W + Gnd
AC Input
AC Output
3-Phase
3W + Gnd
Battery Cabinet
2W + Gnd
UPS Cabinet
Converter
InverterRectifier
Static Bypass
Internal Maintenance Bypass

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Liebert NX and is the answer not in the manual?

Liebert NX Specifications

General IconGeneral
Frequency50/60 Hz
TopologyDouble Conversion/Online
Input Voltage208, 220, 240 VAC
Output Voltage208, 220, 240 VAC
Battery TypeVRLA
Operating Temperature0 to 40°C (32 to 104°F)
Humidity Range0 to 95% (non-condensing)

Related product manuals