Chapter 4: Software Update/Restore 4-11
Step 10: When you reach the Update PLC screen, press F3 (ENTER).
Step 11: Press F4 (PAGE DOWN) until you reach the screen to Restore Bar Feeder Parameters From MMI to PLC, and press F3
(ENTER).
Step 12: The bar feeder parameters will now be saved from the display to the PLC.
Step 13: Press F4 (OK).
Step 14: Turn off power to bar feeder.
Step 15: Move the RUN/STOP switch to RUN position.
Step 16: Restore power to the bar feeder.
Procedure complete.