1-6 Chapter 1: Alarms
QUICK SIX
A003 – Lathe Emergency Stop Line Open
LATHE EMERGENCY
STOP LINE OPEN!
POSSIBLE CAUSES:
- EMERGENCY STOP
PUSHED IN
- WIRING PROBLEM
A003
Description:
The Lathe Emergency Stop Line Open alarm occurs whenever the PLC does not detect input (I0.3). The problem is generated when
the lathe E-stop push button is pressed in.
Solution:
Press the HELP key on the remote control station. Press the F4 (Page Down icon) twice.
Case Input Remote Pendant Solution
1 Bit 3 = 1
MODULE 0
76543210
1000
Alarm needs to be cleared. Press the STOP key on the remote
control station to clear the message and reset the alarm.
2 Bit 3 = 0
MODULE 0
76543210
0
Reset the E-stop push button on the lathe.
For case 2, after the solutions have been completed, press the STOP key on the remote control station to clear the message and
reset the alarm.