EasyManuals Logo

Lucent Technologies DDM-2000 OC-12 User Manual

Lucent Technologies DDM-2000 OC-12
1676 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #146 background imageLoading...
Page #146 background image
363-206-295
Power
Issue 1 December 1997 4-5
Power Distribution 4
See "Power Requirements" in Section 10, "Technical Specifications," for power
dissipation values.
Figure 4-3 shows a typical battery feeder interface for a single shelf.
!
CAUTION:
This information is for a typical application only. Consult 801-525-168,
DDM-2000 Floor Plan Data Sheets, and T-82046-30, Power Systems DC
Distribution Circuit for Digital Transmission System, for proper engineering
of battery plant and feeders.
Figure 4-3. Typical 48 Volt Power Supply for DDM-2000 OC-12 Single Shelf
RTN (A)
RTN (B)
-48 V (A)
-48 V (B)
-48 V (A)RTN (A)RTN (B) -48 V (B)
12 GA
To DDM-2000 Shelf
NOTE
NOTE: Feeder size is selected per T82046-30 and EIM 90MV001, Issue 5.
To Fuse
Protection
At -48 V Battery
Distribution
Fuse Board