9052
PLC Control Object; Change
Window option – disable clearing
PLC register
R/W
Set this bit to prevent the OIT from clearing the PLC register used
for the Change Window option
9053,9054 Reserved for future use
9055
Loss of communications to PLC;
Writing to PLC register control
R/W
If OIT loses connection to the PLC while it is trying to write to a
PLC register, set this bit to continue to send Write command after
communications is reestablished. Clearing this bit prevents the
OIT from issuing the Write command after connection is
reestablished.
0: Any write to PLC command will be killed.
1: Any write to PLC command will be continuously retired.
9056
Loss of communications to PLC;
Touchscreen control
R/W
If OIT loses connection to the PLC, setting this bit disables the
touchscreen until communications is reestablished.
9057-9059 Reserved for future use
9060
Keypad Control; AI or NI located
on left side of keypad window
RdOnly
The OIT sets this bit when user edits a Numeric Input Object or
ASCII Input Object located on the left side of the keypad. The
OIT clears this bit when user presses the Enter or ESC keys.
Note: this bit can be used to control Keypad popup.
9061
Keypad Control; AI or NI located
on left side of keypad window
RdOnly Same as LB9060
9062
Keypad Control; AI or NI located
on left top side of keypad window
RdOnly
The OIT sets this bit when user edits a Numeric Input Object or
ASCII Input Object located on the left side of the keypad on the
top half. The OIT clears this bit when user presses the Enter or
ESC keys.
9063
Keypad Control; AI or NI located
on left bottom side of keypad
window
RdOnly
The OIT sets this bit when user edits a Numeric Input Object or
ASCII Input Object located on the left side of the keypad on the
bottom half. The OIT clears this bit when user presses the Enter
or ESC keys.
9064
Keypad Control; AI or NI located
on right side of keypad window
RdOnly
The OIT sets this bit when user edits a Numeric Input Object or
ASCII Input Object located on the right side of the keypad. The
OIT clears this bit when user presses the Enter or ESC keys.
9065
Keypad Control; AI or NI located
on right side of keypad window
RdOnly Same as LB9064
9066
Keypad Control; AI or NI located
on right top side of keypad
window
RdOnly
The OIT sets this bit when user edits a Numeric Input Object or
ASCII Input Object located on the right side of the keypad on the
top half. The OIT clears this bit when user presses the Enter or
ESC keys.
9067
Keypad Control; AI or NI located
on right bottom side of keypad
window
RdOnly
The OIT sets this bit when user edits a Numeric Input Object or
ASCII Input Object located on the right side of the keypad on the
bottom half. The OIT clears this bit when user presses the Enter
or ESC keys.
9068
Keypad Control; AI or NI located
on any side of keypad window
RdOnly
The OIT sets this bit when user edits a Numeric Input Object or
ASCII Input Object located on any side of the keypad. The OIT
clears this bit when user presses the Enter or ESC keys.
9069
Keypad Control; AI or NI located
on any side of keypad window
RdOnly Same as LB9068
9070-9079 Reserved for future use
9080
Keypad control; AI or NI located
on TOP side of keypad window.
RdOnly
The OIT sets this bit when user edits a Numeric Input Object or
ASCII Input Object located on the TOP side of the touchscreen.
The OIT clears this bit when user presses the Enter or ESC keys.
9081
Keypad Control: AI or NI located
on BOTTOM side of keypad
window.
RdOnly
The OIT sets this bit when user edits a Numeric Input Object or
ASCII Input Object located on the BOTTOM side of the
touchscreen. The OIT clears this bit when user presses the Enter
or ESC keys.
9082-9089 Reserved for future use
9090 Clear Data Event Log R/W
2.6.0 -- This bit is used to clear the event data. Set to clear data.
After it is set, the OIT automatically clears the bit after data is
erased.
9091 Contrast Up Write V 2.6.0 -- Use to increment the contrast.
9092 Contrast Down Write V. 2.6.0 -- Use to decrement the contrast.
9093-9099 Reserved for future use