5
3.4 ELECTRICAL REQUIREMENTS
For  your  safety  and  Ascent  performance,  the  ground  on  this  circuit  must  be 
non-looped.  Please  refer  to  NEC  article  210-21  and  210-23.  Your  Ascent  Trainer 
is  provided  with  a  power  cord  with  a  plug  listed  below  and  requires the  listed 
outlet.  Any  alterations  of  this  power  cord  could  void  all  warranties  of  this 
product.  Multiple  Ascent  trainers  can  be  powered  on  one  dedicated  circuit.  (3 
units per 15 Amp and 4 units per 20 Amp dedicated circuit.)
CHAPTER 3: IMPORTANT SAFETY INSTRUCTIONS 
MATRIX DEDICATED CIRCUIT/ELECTRICAL REQUIREMENT INFO
All  Matrix  Ascent  Trainer  units  require  the  use  of  a  15  amp  or  20  amp 
“dedicated  circuit,”  with  a  non-looped  (isolated)  neutral/ground,  for  the 
power  requirement.  Quite  simply  this  means  that  each  outlet  you  plug  
Ascent  Trainers  into  should  not  have  anything  else  running  on  that  same 
circuit  besides  other  Ascent  or  Incline  trainers  (up  to  3  per  15  amp  circuit 
and  4  per  20  amp  circuit).  The  easiest  way  to  verify  this  is  to  locate  the 
main  circuit  breaker  box,  and  turn  off  the  breaker(s)  one  at  a  time.  Once  a 
breaker  has  been  turned  off,  the  only  thing  that  should  not  have  power  to 
it  are  the  Ascent/Incline  trainers  in  question.  No  lamps,  vending  machines, 
fans,  sound  systems,  or  any  other  item  should  lose  power  when  you  perform 
this test. 
Non-looped  (isolated)  neutral/grounding  means  that  each  circuit  must  have 
an  individual  neutral/ground  connection  coming  from  it,  and  terminating  at 
an approved earth ground. You cannot “jumper” a single  neutral/ground from 
one circuit to the next.   
In  addition  to  the  dedicated  circuit  requirement,  the  proper  gauge  wire 
must  be  used  from  the  circuit  breaker  box,  to  each  outlet  that  will  have  the 
maximum  number  of  units  running  off  of  it.  If  the  distance  from  the  circuit 
breaker  box,  to  each  outlet,  is  100  ft  or  less,  then  12  gauge  wire  may  be 
used.  For  any  distance  greater  than  100  ft  from  the  circuit  breaker  box  to 
the outlet, 10 gauge wire must be used.
5