264
3: Reserved
4: V/F complete separation
5: V/F half separation
P24.01
Torque boost
0.0 to 50.0
0.0
P24.02
Cut-off frequency of torque boost
0.00 Hz to P02.11
10.00 Hz
P24.03
Multi-point V/F frequency 1
0.00 Hz to P24.05
0.00 Hz
P24.04
Multi-point V/F voltage 1
0 V to P24.06
0 V
P24.05
Multi-point V/F frequency 2
P24.03 to P24.07
0.00 Hz
P24.06
Multi-point V/F voltage 2
P24.04 to P24.08
0 V
P24.07
Multi-point V/F frequency 3
P24.05 to 599.00
0.00 Hz
P24.08
Multi-point V/F voltage 3
P24.06 to 380
0 V
P24.09
Slip compensation coefficient
0.0 to 100.0
0.0
P24.10
V/F overexcitation gain
0.0 to 100.0
0.0
P24.11
Oscillation suppression gain
0 to 100
10
P24.12
Oscillation suppression gain mode
0 to 2
0
P24.13
Voltage source for V/F separation
0 to 9
0
0: Digital setting
1: AI1
2: AI2
3: Reserved
4: HDI
5: Multi-reference
6: Simple PLC
7: PID
8: Modbus
9: PROFINET
P24.14
Digital setting of voltage source for V/F
separation
0 to 1000
0 V
P24.15
Voltage rise time of V/F separation
0.0 to 6000.0
5.0 s
P24.16
Voltage fall time of V/F separation
0.0 to 6000.0
5.0 s