259
When you rotate “ ” clockwise, the function code displays the switched parameter number, only RAM modified and
not save to EEPROM.
P16.05
Line speed display coefficient
0.1 to 999.9%
100.0%
This function code is used to correct the line speed display error, and has no influence on the actual speed.
P16.05speed LineP01.42
P16.06
Rotation speed display coefficient
0.1 to 999.9%
100.0%
This function code is used to correct the rotation speed display error, and has no influence on the actual speed.
pairs polemotor ofnumber /P16.06frequency running displayed60speedrotation Mechanical
P16.07
Frequency display coefficient
0.0 to 100.0%
100.0%
P01.57=P01.05*Frequency display coefficient
7.18 P20: Motor 2 parameters
P20.00
Motor type selection
0 to 1
0
0: Asynchronous motor
1: Synchronous motor
P20.01
Asynchronous motor rated
power
0.1 to 3000.0 kW
Model dependent
P20.02
Asynchronous motor rated
voltage
0 to 1200 V
Model dependent
P20.03
Asynchronous motor rated
current
0.8 to 6000.0 A
Model dependent
P20.04
Asynchronous motor rated
frequency
0.01 Hz to P02.10
50.00 Hz
P20.05
Asynchronous motor rated
speed
1 to 36000 rpm
Model dependent
P20.06
Asynchronous motor stator
resistance
0.001 to 65.535
Ω
Model dependent
P20.07
Asynchronous motor rotor
resistance
0.001 to 65.535
Ω
Model dependent