AUTO RECORD A / B Setpoints
Use Auto Record A Setpoint (P334) and Auto Record B Setpoint (P335) to define the
boundaries within which the level must be, for the resultant Echo Profile to be
considered for an Auto Profile Record.
If "----" is displayed for either P334 or P335, Auto Profile Records are saved
regardless of current level (subject to all other restrictions).
Enter the level value in Units (P004) or percent of Span (P007) as referenced to
Empty (P006). (Ensure the % Symbol is displayed before attempting to enter a value
in percent, see PROGRAMMING Keypad).
P334 (G) AUTO RECORD A SETPOINT
Enter the critical level which, in conjunction with Auto Record B Setpoint,
defines the boundaries for Auto Profile Records to be saved.
values: -999 to 9999
P335 (G) AUTO RECORD B SETPOINT
Enter the critical level which, in conjunction with Auto Record A Setpoint,
defines the boundaries for Auto Profile Records to be saved.
values: -999 to 9999
P336 (G) AUTO RECORD FILLING / EMPTYING
Use this feature to restrict Auto Profile Records from being saved unless
the level is rising, falling or either.
If the level changes at a rate in excess of the corresponding Filling / Emptying
Indicator (P702 / P703) values, the Echo Profile is saved subject to this and
other Auto Profile Record restrictions.
values: 0 = Auto Profile Record on filling or emptying (preset)
1 = Auto Profile Record on filling only.
2 = Auto Profile Record on emptying only.
P337 (G) AUTO RECORD LOE TIME
Use this feature to restrict Auto Profile Records from being saved unless an
extended loss of echo (LOE) condition occurs.
If the LOE condition exceeds the period entered (in seconds) the Echo Profile
is saved, subject to this and other restrictions.
When set for "0" (preset), LOE is not required for an Auto Profile Record
to be saved.
values: 0.0 to 9999
PROGRAMMING
PARAMETERS
PL-507 103