P331 (G) AUTO RECORD ENABLE
Use this feature (if desired) to enable / disable the Auto Profile
Record function.
values: 0 = off
1 = on
P332 (G) AUTO RECORD TRANSDUCER
Use this feature (if desired) to specify the Transducer Point Number for
which Auto Profile Records are saved.
This feature is preset to Point Number 1. (Alteration is only required if
"differential" or "average" Operation (P001 = 4 or 5) is selected).
values: 0 = any Transducer
1 = Transducer 1 (preset)
2 = Transducer 2
P333 (G) AUTO RECORD INTERVAL
Enter the time (in minutes) to elapse after an Auto Profile Record is saved
before another Auto Profile Record can be saved (subject to all
other restrictions).
values: 0.000 to 9999 (preset to 120 minutes)