P607 (G) FLOWRATE DECIMAL
Enter the maximum number of decimal places to be displayed.
In the RUN mode, the number of decimal places displayed is automatically
adjusted (if necessary) to prevent the number of Flowrate digits from
exceeding display capabilities.
( The max. number of "head" decimal places is controlled by
Decimal Position [ P060 ] ).
values: 0 = no digits after the decimal point
1 = 1 digit after the decimal point
2 = 2 digits after the decimal point
3 = 3 digits after the decimal point
P608 OCM UNITS
This parameter is enabled only if the primary measuring device (P600)
supports absolute calculations.
values:
ratiometric
0 = ratiometric calculation (units defined by P604)
absolute
1 = litres / second
2 = cubic metres / hour
3 = cubic metres / day
4 = cubic feet / second
5 = gallons / minute – imperial
6 = million gallons / day – imperial
7 = gallons / minute – U.S.
8 = million gallons / day – U.S.
PARAMETERS
PL-507 115