ADVANCED SHOT ADJUSTMENT (P840-P845, P850 to P852)
P840 SHORT SHOT NUMBER
Enter the number of short shots to be fired (and results averaged)
per transmit pulse.
values: 0 to 100
P841 LONG SHOT NUMBER
Enter the number of long shots to be fired (and results averaged) per
transmit pulse.
This value is automatically altered by Measurement Response (P003).
values: 0 to 200
P842 SHORT SHOT FREQUENCY
Adjust the short shot transmit pulse frequency (in kHz).
This feature is automatically altered when Transducer (P004) is altered.
values: 10.00 to 60.00
P843 LONG SHOT FREQUENCY
Adjust the long shot transmit pulse frequency (in kHz).
This feature is automatically altered when Transducer (P004) is altered.
values: 10.00 to 60.00
P844 SHORT SHOT WIDTH
Adjust the width (in ms) of the short shot transmit pulse.
This feature is automatically altered when Transducer (P004) is altered.
values: 0.000 to 5.000
P845 LONG SHOT WIDTH
Adjust the width (in ms) of the long shot transmit pulse.
This feature is automatically altered when Transducer (P004) is altered.
values: 0.000 to 5.000
PL-507 142