P850 SHORT SHOT BIAS
Use this feature to slant the echo evaluation in favour of the short shot echo
when both short and long shots are evaluated (see Shot Mode, P803). This
feature is preset to 20.
values: 0 to 100
P851 SHORT SHOT FLOOR
Enter the minimum echo strength (in dB above 1 uV), derived from a short
shot, to be considered for evaluation. This feature is preset to 50.
values: 0 to 100
P852 SHORT SHOT RANGE
Enter the maximum distance in Units (P005) to be measured using
short shot echoes.
This feature is automatically altered when Transducer (P004) is altered.
values: 0.000 to 9999