PARAMETER VALUE OPTIONS
Operation 1 = "level", Full = 100% Reading = 20 mA (most common)
(P001) = 2 = "space", Empty = 100% Reading = 20 mA (less common)
3 = "distance", (references measurements to transducer face)
4 = "DPD", (displays differential level, 2 transducers required)
5 = "DPA", (displays average level, 2 transducers required)
6 = "OCM", (calculates flowrate for head and total flow volume)
7 = "PT", (calculates total pumped volume)
Material 1 = "liquid", flat perpendicular reflective surface (most common)
(P002) = 2 = "solid", angled rough reflective surface (for heaping solids)
Measurement 1 = "0.1 m/min", very slow moving surface (less common)
Response 2 = "1.0 m/min", typical liquid surface (usual setting)
(P003) = 3 = "10 m/min", very fast moving surface (less common)
Transducer 0 = "out-of-service"
(P004) 1 = "ST-25"
2 = "ST-50"
100 = "ST-H"
101 = "XCT-8" Enter the appropriate transducer type
102 = "XPS-10"
103 = "XCT-12"
104 = "XPS-15"
250 = "mA input"
Units 1 = "metres"
(P005) = 2 = "centimetres"
3 = "millimetres" Enter the linear dimension units desired
4 = "feet"
5 = "inches"
Empty
(P006) = "0.000" to "9999" Enter value in P005 Units
Span
(P007) = "0.000" to "9999" Preset by P006, change if desired.
Date
(P008) = "00:01:01" to "99:12:31"
Time
(P009) = "00:00:00" to "23:59:59"
With General Application programming complete, a System Performance Evaluation
(see OPERATION ) is recommended before proceeding to the following Application
programming examples.
OPERATION
APPLICATIONS
PL-507 41