P004 (G) TRANSDUCER
Enter the type of transducer(s) connected to the HYDRO+.
values: 0 = not entered 100 = STH 103 = XCT-12
1 = ST-25 101 = XCT-8 104 = XPS-15
2 = ST-50 102 = XPS-10 (preset) 250 = auxiliary
(see mA Input)
P005 (G) UNITS
Enter the units of measure desired for programming and/or display.
values: 1 = metres (m) (preset) 4 = feet (ft)
2 = centimetres (cm) 5 = inches (in)
3 = millimetres (mm)
P006 EMPTY
Enter the maximum transducer face to surface distance, in Units (P005).
For mA input applications ( P004 = 250 ), set Empty value equal
to Span ( P007 ).
values: 0.000 to 9999 (preset to 8.000 m, or equivalent)