STORM CONDITIONS (P150 to P152)
These features permit a Storm Condition to be defined, to operate a relay
set for the "Storm Control" Relay Function (P111), or modify the operation
of a relay set for any "Pump Control", per Storm Action.
Enter Storm A / B Setpoints similar to Relay A / B Setpoints (P112/P113).
A Storm Condition is considered to be in effect if the current level is:
(a) above the Storm A Setpoint (which is higher than Storm B Setpoint).
(b) below the Storm A Setpoint (which is lower than Storm B Setpoint).
P150 STORM A SETPOINT
Enter the value (similar to Relay A Setpoint, P112) to define a Storm
Condition (in conjunction with Storm B Setpoint).
values: 0.000 to 9999
P151 STORM B SETPOINT
Enter the value (similar to Relay B Setpoint, P113) to define a Storm
Condition (in conjunction with Storm A Setpoint).
values: 0.000 to 9999
P152 STORM ACTION
Use this feature to disable a pump for which Storm A / B Setpoints have been
entered, to prevent futile running or potential damage due to pumping during
flood conditions, (when a Storm Condition exists).
values: 0 = off (pumps are disabled during a Storm Condition).
1 = on (normal operation during a Storm Condition, preset).
P153 STORM MAX DURATION
Use this feature to define the maximum time (in minutes) pumps may be
disabled by Storm Action (P152).
values: 0.000 to 9999 (preset = 30 minutes)
PL-507 86