LCD TOTALIZER (P322 and P323)
Use these features to view, reset, or preset the 8 digit display totalizer.
These features may be enabled if Operation is set for "OCM" or "Pumped
Volume" (P001 = 6 or 7).
The 8 digit totalizer display is divided into 2 groups of 4 digits in the program mode.
For this reason, the 4 least significant totalizer digits are stored in one parameter and
the 4 most significant digits are stored in another.
e.g. P323 & P322 = 8 Digit Value
0017 6.294 = 176.294
Totalizer units are dependent upon programming.
Enter "0" (if desired) when these parameters are accessed, to reset the totalizer to
zero. Alternatively, enter any other (applicable) value, to preset the totalizer to the
value desired.
During operation, these values are dynamic (continuously changing). Once per hour,
the dynamic value is stored in non-volatile EEPROM memory. Therefore, in the event
of a power interruption, upon power resumption, the value will be correct to within at
least 60 minutes prior to the interruption.
If desired, connect a backup dc power source to the HYDRO+ to ensure the totalizer
value is not affected by an ac power interruption.
(See INSTALLATION Interconnection / Power).
P322 LCD TOTAL LOW
View and / or alter the 4 least significant digits of the totalizer value.
values: 0.000 to 9999
P323 LCD TOTAL HIGH
View and / or alter the 4 most significant digits of the totalizer value.
values: 0000 to 9999