Page #113 background imageLoading...
Page #113 background image
FleX-Net
TM
Installation and Operation Manual
109
QMP-5101N/V Network Paging Wiring
Figure 77: QMP-5101N/V Network Master Paging Control Module Wiring to the
ANC-5000 Audio Network Controller Module
JW7
JW8
+ - + -
S - +
S - +
S - + S - + L - +
PAGING BUS
MIC
PTT
OUT
IN
ANC-5000 Audio Network
Controller Module
+
+
--
S
PTT
MIC
Master microphone
and push to talk button
are wired by Factory to
these terminals
QMP-5101N/V Network
Master Paging Module
+
-
Remote
Power
Input
(24V DC
Regulated
1.7 A max)
FX-2000N
Fire Alarm
Aux. Power
Supply
G.A.
Input
IN
RS-485
NOT USED
Wire the Paging Bus
to all other ANC-5000
Audio Network
Controller Modules
OUT to IN, see Figure
73 for more details.
TWISTED
SHIELDED
PAIR CABLE
Jumpers JW7 and JW8
are normally installed
(shorted).
This connection to Aux
Power is required when
the ANC-5000 is
mounted over an
FX-2009-12N Fire Alarm
board.