EasyManua.ls Logo

Mircom FX-401

Mircom FX-401
91 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
82
10.0 Appendix C - Reporting
10.1 Ademco Contact-ID FX-400 Series Event Codes
Table 19 Contact-ID Event Codes
Event Description Event
Family
Qualifier Code Group # Contact #
Phone Line #1 trouble detected Trouble New event 1 351 00 000
Phone Line #2 trouble detected Trouble New event 1 352 00 000
Phone Line #1 trouble restored Trouble Restore 3 351 00 000
Phone Line #2 trouble restored Trouble Restore 3 352 00 000
Failure to report to an Account Trouble New event 1 354 Acct # Acct #
Report to an Account successful Trouble Restore 3 354 Acct # Acct #
RS-485 Communication Trouble Trouble New event 1 350 00 485
Periodic (24 hr) Test Event (NORMAL) Test New event 1 602 00 000
Periodic (24 hr) Test Event (OFF
NORMAL)
Test New event 1 608 00 000
Manually initiated dialer test Test New event 1 601 00 000
Zone Fire Alarm Alarm New event 1 110 00 NNN
Zone Fire Alarm restored Alarm Restore 3 110 00 NNN
Zone Trouble detected Trouble New event 1 300 00 NNN
Zone Trouble restored Trouble Restore 3 300 00 NNN
Zone Supervisory condition Supervisory New event 1 200 00 NNN
Zone Supervisory restored Supervisory Restore 3 200 00 NNN
Water flow Alarm New event 1 113 00 NNN
Water flow restored Alarm Restore 3 113 00 NNN
Indicating Zone Trouble Trouble New event 1 320 00 NNN
Indicating Zone Trouble restored Trouble Restore 3 320 00 NNN
General Alarm Alarm New event 1 140 00 NNN
General Alarm restored Alarm Restore 3 140 00 NNN
AC power lost Trouble New event 1 301 00 000
AC power restored Trouble Restore 3 301 00 000
Battery Low Trouble New event 1 302 00 000
Battery Low restored Trouble Restore 3 302 00 000
Ground Fault Trouble New event 1 310 00 000
Ground Fault restored Trouble Restore 3 310 00 000

Table of Contents

Related product manuals