The panel can provide up to 280mA of current to the devices on the loop at normal standby.
For device currents see Appendix E - Battery Calculations on page 86.
For further information refer to the device Installation Instructions and other documentation
provided with the addressable devices, bases, and isolators.
5.1.4 Drift Compensation
Drift Compensation is built into MGC addressable devices, and is not performed by the panel.
Drift Compensation automatically adjusts for gradually increasing effects of dust and other
accumulations of dirt in the detectors. It will adjust the thresholds to compensate for a detector
going dirty according to the gradual change in the normal clean air value received. When it can
no longer compensate for an increasingly dirty detector, a dirty detector trouble is indicated for
that device.
5.1.5 Auto Test
Periodically each detector is commanded to return an alarm value to test its ability to alarm. If
the device fails the test, a trouble is indicated on that device. This trouble is latched until
system reset.
5.2 Configurable Input Types
Input devices and modules may be configured as one of many possible input types. Table 9
identifies the device types assignable to each input type. For device type descriptions see
sections 5.2.1 to 5.2.12.
Table 9 Configurable Input Types
Input Type
As listed in
Configurator
Description
located in
Section number
Device Types
Detectors
Dual Input Module
Mini Dual Input Module
Conventional Zone
Module
Alarm Input Alarm Input 5.2.1 XX
Latched Supervisory Latched Supv 5.2.2 XX
Building/Property Safety
Input
Building 5.2.3 XX
Non-Latching
Supervisory
Non-Latch Supv 5.2.2 XX
Priority Alarm Priority Alm 5.2.4 XX
Trouble Input Trouble Input 5.2.5 XX
Waterflow Alarm Input Waterflow 5.2.6 X
System Reset Sys Reset 5.2.7 X
Fire Drill Fire Drill 5.2.7 X
Acknowledge Ack 5.2.7 X
Total Evacuation Total Evac 5.2.7 X
Auxiliary Disconnect Aux Disc 5.2.7 X

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mircom FX-401 and is the answer not in the manual?

Mircom FX-401 Specifications

General IconGeneral
BrandMircom
ModelFX-401
CategoryControl Panel
LanguageEnglish

Related product manuals