9 CREATING A HARDWARE LOGIC
9.2 Multi Function Counter Block
129
9
Output
The following table shows the outputs of the multi function counter block.
*1 Only the "Event" terminals of multi function counter blocks can be linked.
*2 Any of "SI " terminals can be linked.
When a 16-bit multi function counter block is arranged in the hardware logic outline window, two 16-bit counter
timer blocks are arranged in the multi function counter block detail window. These two counter timer blocks
can be simultaneously used. However, OR processing is executed on the outputs of these two counter timer
blocks because a multi function counter block has only one output terminal.
Variable name Data type Linkable block Output value Description
Output 0 Bit External output
SI device
*2
0, 1 The output terminal is for external output signals and
interruption.
Event 0 Bit Multi function counter
*1
0, 1 The output terminals are for events. The "Event 2" and
"Event 3" terminals can be used in 16-bit multi function
counter blocks only. The linkable blocks differ for each
Event terminal in the multi function counter block detail
window. ( Page 167 Event output terminal)
Event 1
Event 2
Event 3
Cam Output Bit External output 0, 1 The output terminals are for external output signals.
These terminals can be used in 32-bit multi function
counter blocks only.