9 CREATING A HARDWARE LOGIC
9.2 Multi Function Counter Block
Parameter
The following table shows the parameters of the cam switch block.
*1 The valid range is determined by the type of the multi function counter block arranged in the hardware logic outline window.
The following table shows "User Address" used for the parameters.
Variable name Data type Valid range Default value Description
Number of Step Word 1 to 16 1 Set the number of steps of the cam switch. A step
indicates the point in which the Low state is switched
to the High state or the High state is switched to the
Low state. The valid Step No. is determined
according to the set value of "Number of Step".
Lower Limit Word The value set with "Lower Limit" in the counter timer
block is applied.
Change the setting value in the counter timer block.
Lower Limit Output State Word Low
High
Low Set the initial state of output. When "Count Value" of
the counter timer block is less than the input value of
"Step No.0", the output status turns to the initial state.
The output status of "Step No.0" or later inverts to the
High state or the Low state for every step No.
Step No.0 Word -2147483648 to 2147483647
(32-bit signed counter)
*1
0 to 4294967295 (32-bit
unsigned counter)
*1
0 Compares the values of step numbers with "Count
Value" in the counter timer block. When "Count
Value" is equal to or larger than the input value, the
previous status is inverted.
Step No.1 Maximum value in
the valid range
Step No.2
Step No.3
Step No.4
Step No.5
Step No.6
Step No.7
Step No.8
Step No.9
Step No.10
Step No.11
Step No.12
Step No.13
Step No.14
Step No.15
Upper Limit Word The value set with "Upper Limit" in the counter timer
block is applied.
Change the setting value in the counter timer block.
Variable name Data type Valid range Default value Description
User Address Word 1000 to 1098 User Address Only even addresses can be assigned to the
parameters of two words (32 bits).